4.2.3.4

Grounding the System

Ground the system as described.
4.2.3.4.1

Not for U.S.: Grounding the System

Grounding: Grounding options
Danger
7
Each HiPath 3800 system cabinet and all external main distribution frames (for ex-
ample, MDFU-E) must be grounded as shown in Figure 4-5 by a separate ground
conductor (minimum cross-section = 2.5 mm
is securely installed and strain-relieved.
If external factors can impact on the ground conductor and if protected installation is
not possible, the ground conductor must have a minimum cross-section of 4 mm
Failure to follow these instructions can result in electrical shock.
The illustrations starting with Figure 4-6 show different grounding options.
Danger
7
If your personnel are not qualified to work on the low-voltage network (230 Vac), you
must hire a licensed electrician to ground the system separately using option 1b
(Figure 4-7).
Note on possible ground loops
To avoid ground loops from remotely operated devices (V.24 system peripherals),
>
the devices should be connected to the same low-voltage network (sub-distribution
board) if possible.
If the building floor plan does not permit this, you may need a line driver to isolate
the external devices in the event of a malfunction.
P31003-H3550-S403-4-7620, 02/05
HiPath 3000 V5.0, HiPath 5000 V5.0, Service Manual
Installing HiPath 3000
Installing HiPath 3800
2
). Make sure that the ground conductor
inst_h3.fm
2
.
4-15