5.12.7

BACnet MS/TP protocol

Using BACnet MS/TP protocol, communication operation and parameter setting are available from
the RS-485 terminals of the inverter.
Pr. No.
52
M100
774
M101
775
M102
776
M103
331
N030
332
N031
390
N054
549
N000
726
N050
727
N051
728
729
When the set value is outside of the setting range, the initial value is applied.
When the Auto baudrate is used, the communication speed is changed to the detected commu-
nication speed.
5 - 506
Name
Operation panel main
monitor selection
Operation panel monitor
selection 1
Operation panel monitor
selection 2
Operation panel monitor
selection 3
RS-485 communication
station number
RS-485 communication
speed
% setting reference
frequency
Protocol selection
Auto Baudrate/Max Master
Max Info Frames
Device instance number
(Upper 3 digit)
Device instance number
(Lower 4 digit)
Initial
Setting Range Description
Value
0, 5 to 14, 17,
18, 20, 23 to 25,
0
34, 38, 40 to 45,
50 to 57, 61, 62,
64, 67 to 69
1 to 3, 5 to 14,
17, 18, 20, 23 to
25, 34, 38, 40 to
9999
45, 50 to 57, 61,
62, 64, 67 to 69,
The count of the setting values "82" and "83"
81 to 96, 98,
returns to "0" if the count exceeds "9999". The
100
upper limit of the count of the setting value
"84" is "9999".
0
Set the inverter station number (node).
0 to 127
Set the communication speed.
The setting value × 100 equals the
96, 192, 384,
96
communication speed.
576, 768, 1152
For example, the communication speed is 9600
bps when the setting value is "96".
50Hz
1 to 590 Hz
Set a reference frequency of the set frequency.
0
Mitsubishi inverter (computer link) protocol
60
50
1
MODBUS® RTU protocol
Hz
Hz
2
BACnet MS/TP protocol
Auto baud rate (bit7)
0: Inactive
1: Active)
255
0 to 255
Max Master (bit0 to bit6) setting range: 0 to 127
Maximum address for master node
Set the maximum number of frames that the
1
1 to 255
inverter can transmit while it owns the token.
Device identifier
0 to 419
0
(0 to 418)
When the combination of Pr.728 and Pr.729 is not
within "0 to 4194302", the setting is out of range.
Example:
When Pr. 728 = "419", setting range of Pr. 729 is "0
0 to 9999
0
to 4302".
(0 to 4302)
When Pr. 729 = "4303" or more, setting range of
Pr. 728 is "0 to 418".
81: BACnet reception status
82: BACnet token pass counter
(Displays the count of received token)
83: BACnet valid APDU counter
(Displays the count of valid APDU detection)
84: BACnet communication error counter
(Displays the count of communication error)
85: Terminal FM/CA output level
(Same display as Analog output 0)
86: Terminal AM output level
(Same display as Analog output 1)