11.2.2

Replacing fuses

NOTICE
Every time a fuse blows, all of the arm fuses must be replaced.
For units >850 A, as described here, these are the fuses installed in the unit.
For units ≤850 A, these are the externally installed fuses.
Replacing fuses for 900 A to 1200 A units
The fuses are accessible from the front after removing the front cover and swiveling the
support plate for the electronics out of the way. The fuses are fixed with 2 hex screws each
Figure 11-9
Replacing fuses for 900A to 1200 A units
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
(width across flats 16). Tightening torque 25 Nm.
Maintenance
11.2 Replacing components
519