Dc Electrical Specifications Mps Standard Cabinet - Avaya Media Processing Server 1000 Hardware Installation And Maintenance

Hide thumbs Also See for Media Processing Server 1000:
Table of Contents

Advertisement

Nominal Input
Plug Type
Number of Feeds
Cord Length
Input Current (Amps)
Total Power
System Console
Voltage Range
Current/Power Consumption

DC Electrical Specifications MPS Standard Cabinet

Nominal Input
Voltage Range
Plug Type
Number of Feeds/
Pairs
Input Current (Amps)
Total Power
Note:
The DC Power Distribution Unit (DC PDU) is intended to provide redundant power. In case of one leg
failure, the total current (leg 1 + leg 2) cannot exceed the single leg rating of 30 Amps. Total current
depends on equipment configuration.
October 2014
115 Volts AC Single Phase
NEMA L5-20P plug 15 AMP Rated
Cord
2 min (4 max)
14.7 Feet (4.5 meters)
12 Amps Typical 60 Amps Maximum
(Total all feeds)
2100 Watts (Typical Configuration) 3000 Watts (Maximum Configuration)
100 – 240 AC
1.8 - 0.9 Amps
216 Watts
-48 Volts DC (Terminal
Block)
-40 to -56 VDC
AMP #52043-3 or
equivalent
2 min
60 Amps max
150 Amps max See Note:
2100 Watts (Typical
configuration) 3000 Watts
(Maximum configuration)
Avaya Media Processing Server 1000 Hardware Installation and Maintenance
Comments? infodev@avaya.com
DC Electrical Specifications MPS Standard Cabinet
230 Volts AC Single Phase
NEMA L6-20P 15 AMP Rated Cord
2 min (4 max)
14.7 Feet (4.5 meters)
6 Amps Typical 60 Amps Maximum
(Total all feeds)
-48 Volts DC (PDU)
-40 to -56 VDC
ETC Molex p/n
HDCL-6142-CC or
equivalent
2 min (6 max)
26 Amps/PDU Typical (13
Amps/feed)
200 Amps max See Note
2:
-48 Volts DC Breaker
Panel
-40 to -60 VDC
Panduit (LCDX6-14A-L),
T&B (54205), FCI
(YAV4CL-2TC14-FX) or
equivalent
4
100 Amps max (per
breaker)
235