Installation
Required tools
You need the following tools to do the installation:
Phillips #2 screwdriver
●
ESD grounding wrist strap
●
Antistatic mat
●
Electrical specifications
Parameter
Input
Nominal voltage range
●
Maximum current AC RMS
●
AC operating range
●
Nominal frequencies
●
Maximum DC power output
Maximum system AC power
consumption
Maximum system heat dissipation
Volt-ampere rating
Wall plug type
United States
●
Non-United States
●
CPU plug type
22
Avaya CMS Sun Fire V880/V890 Installation, Maintenance, and Troubleshooting
Value
V880
100-240 V AC,
●
autoranging
15.0 A @100 VAC
●
90-264 V rms, 47-63Hz
●
50 Hz or 60 Hz
●
2240 W
3000 W
10308 BTU/hr
1515 VA with 1120 Watt load
(PF=0.99)
NEMA 5-15P
●
Power cords must be
●
obtained locally
IEC 320
V890
200-240 V AC,
●
autoranging
8.0 A @200 VAC
●
180-264 V rms, 47-63Hz
●
50 Hz or 60 Hz
●
2509 W
3200 W
10912 BTU/hr
2078 VA with 1629 Watt load
(PF=0.98)
NEMA 6-15P
●
Power cords must be
●
obtained locally
IEC 320
May 2006