Required Tools; Electrical Specifications - Avaya Sun Fire V880 Installation & Maintenance

Hardware installation, maintenance, and troubleshooting
Hide thumbs Also See for Sun Fire V880:
Table of Contents

Advertisement

Installation

Required tools

You need the following tools to do the installation:
Phillips #2 screwdriver
ESD grounding wrist strap
Antistatic mat

Electrical specifications

Parameter
Input
Nominal voltage range
Maximum current AC RMS
AC operating range
Nominal frequencies
Maximum DC power output
Maximum system AC power
consumption
Maximum system heat dissipation
Volt-ampere rating
Wall plug type
United States
Non-United States
CPU plug type
22
Avaya CMS Sun Fire V880/V890 Installation, Maintenance, and Troubleshooting
Value
V880
100-240 V AC,
autoranging
15.0 A @100 VAC
90-264 V rms, 47-63Hz
50 Hz or 60 Hz
2240 W
3000 W
10308 BTU/hr
1515 VA with 1120 Watt load
(PF=0.99)
NEMA 5-15P
Power cords must be
obtained locally
IEC 320
V890
200-240 V AC,
autoranging
8.0 A @200 VAC
180-264 V rms, 47-63Hz
50 Hz or 60 Hz
2509 W
3200 W
10912 BTU/hr
2078 VA with 1629 Watt load
(PF=0.98)
NEMA 6-15P
Power cords must be
obtained locally
IEC 320
May 2006