MPS 1000 System Hardware Overview
The dual BE PDU consists of two identical seven-outlet control boxes. Each control box can deliver
15 amps total and is protected by a 15-Amp circuit breaker. The number of usable connections
depends on the amperage draw (not voltage) of the attached equipment. Typically, five connections
are permitted. Each BE PDU has seven power outlet ports and one power inlet port. The power
outlet ports are IEC 320-C13s, which accommodate equipment line cords. The power inlet port is an
IEC 320-C19 port, which can use three different types of inlet line cord. The type of inlet line chord
depends on the connectivity desired. The types of inlet line cord are:
• L5-20P for 115 Vac connector
• L6-20P for 230 Vac connector
• IEC 320-C19 to IEC 320-C20 connector for FE PDU connectivity
Up to five of the following application or Speech Servers can be placed on a single BE PDU:
• IBM x3550
• HP DL360-G5, HP DL360-G7
• Solaris: V215, V245, Netra 240, T2000, T5120, T5220, Netra T4-1
Additional devices, such as KVM, fans, and switches, can share the BE PDU only if they do not
exceed the 15 amp maximum, regardless of voltage.
Redundant Power Supplies
Back end PDU supporting redundant power supplies must be attached to different front end PDU as
shown in the following example.
Avaya Media Processing Server 1000 Hardware Installation and Maintenance
32