3 Specifications and Application Procedures
Procedure
Turning ON
Turning ON the
Power and
Unit Power Sup-
Going Online
ply to the Slave
from the Sys-
Terminal
mac Studio
Turning ON the
I/O Power Sup-
ply to the Slave
Terminal
8
Turning ON the
Power Supply to
the NJ-series
Controller
Online connec-
tion from Sys-
mac Studio
Comparing
Comparing and
and Merging
Merging with the
with the Actual
Actual Network
Network Con-
Configuration or
figuration or
the Actual Unit
9
the Actual Unit
Configuration
Configuration
Downloading
Downloading
the Network
the Network
Configuration
Configuration
Information,
Information, the
10
the Slave Ter-
Slave Terminal
minal Setting
Setting Informa-
Information,
tion, and the
and the User
User Program
Program
3 - 10
Item
Turn ON the Unit power supply to the EtherCAT Coupler Unit
and to any Additional NX Unit Power Supply Units that are
used. When you do, the Unit configuration information does
not exist in the EtherCAT Coupler Unit yet, so the TS indica-
tor on the EtherCAT Coupler Unit will flash green.
Turn ON the I/O power supply to the EtherCAT Coupler Unit
and to any Additional I/O Power Supply Units that are used.
Turn ON the power supply to the NJ-series Controller.
Use the Sysmac Studio to set communications with the
NJ-series Controller and go online.
Use the compare and merge operation for the physical con-
figurations to see if the EtherCAT network configuration and
EtherCAT Slave Terminal Unit configuration that are set on
the Sysmac Studio agree with the actual configurations.
Download the network configuration information (EtherCAT
slave setting information) and the Slave Terminal setting
information (Unit configuration information, I/O allocation
information, Unit operation settings, and Unit application
data). Use the synchronization operation of the Sysmac Stu-
dio to download the data.
Description
NX-series EtherCAT Coupler Unit User's Manual (W519)
Reference
4-2 Indicators on
page 4-5
---
---
Sysmac Studio
Version 1 Opera-
tion Manual
(W504)
• 9-2-7 Sysmac
Studio Functions
Used as
Required on
page 9-25
• NJ-series CPU
Unit Built-in
EtherCAT Port
User's Manual
(W505)
9-4 Transferring
and Comparing
Settings on page
9-34

Advertisement

Table of Contents
loading