Omron NX-ECC201 User Manual page 398

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

Appendices
Index
Subindex
(hex)
(hex)
5000
---
Communications Error
Setting
00
Number of Entries
01
Consecutive Commu-
nications Error Detec-
tion Count
• Subindex 01 hex sets the number of consecutive communications errors to detect before generating
a communications data error. A Communications Synchronization Error occurs when the number of
consecutive communications errors exceeds this setting.
Index
Subindex
(hex)
(hex)
5001
---
Sync Not Received
Timeout Setting
00
Number of Entries
01
Sync Error Monitoring
Time
• Subindex 01 sets the time until a synchronization error is generated. A Synchronization Error occurs
if the first SYNC0 signal input does not turn ON within this set time after the EtherCAT Coupler Unit
enters the Safe-Operational state.
A value of 0 implies 120 s.
A - 58
Object name
Default
---
1
1
Object name
Default
---
1
0
Data range
Unit
Data type
---
---
---
1
---
USINT
0 to 15
---
USINT
Data range
Unit
Data type
---
---
---
1
---
USINT
0 to 600
s
UINT
NX-series EtherCAT Coupler Unit User's Manual (W519)
I/O allo-
Data
Access
cation
attribute
---
---
---
RO
Not
---
possi-
ble.
RW
Not
Y
possi-
ble.
I/O allo-
Data
Access
cation
attribute
---
---
---
RO
Not
---
possi-
ble.
RW
Not
Y
possi-
ble.

Advertisement

Table of Contents
loading