6 Installation
If the DIN Track is made of steel and the surface is not treated to produce an insulating material, you
can omit grounding the functional ground terminal on any Unit that has one, as shown in the following
figures.
• DIN Track Made of Steel and Surface Not Insulated
EtherCAT
Slave
Terminal
DIN Track
(a) Independent Grounds: Best
 Precautions when Grounding
• To prevent influence from leakage current from other electrical devices, electrically isolate the
panel in which the EtherCAT Slave Terminal is housed from other devices.
• If high-frequency equipment is present, then ground not only the high-frequency equipment but
also the panel itself in which the EtherCAT Slave Terminal is housed.
• To ground the shield wire when using shielded cables for I/O wiring, wire the ground according the
shield treatment specifications for the NX Unit that is used.
Wire communications cables according to the shield treatment specifications for the Unit.
6 - 32
DIN Track
Other
device
Ground to
100 Ω or less
OK
(b) Common Ground: Acceptable
EtherCAT
Slave
Terminal
DIN Track
Other
device
OK
NX-series EtherCAT Coupler Unit User's Manual (W519)
EtherCAT
Slave
Terminal
Other
device
NG
(c) Common Ground: Incorrect