Omron NX-ECC201 User Manual page 294

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

13 Troubleshooting
Event code
Event name
35070000 hex
PDO WDT
Setting Error
35080000 hex
SM Event
Mode Set-
ting Error
35090000 hex
TxPDO Map-
ping Error
350A0000 hex
RxPDO Map-
ping Error
350B0000 hex
Illegal State
Transition
Request
Received
350C 0000 hex
Error State
Transition
Received
350D 0000 hex
Synchroniza-
tion Cycle
Setting Error
84C0 0000 hex
NX Unit
Communica-
tions Timeout
84C1 0000 hex
NX Unit Ini-
tialization
Error
85000000 hex
Process Data
WDT Error
85010000 hex
Synchroniza-
tion Interrup-
tion Error
13 - 16
Meaning
Assumed cause
An incorrect PDO
• An incorrect PDO WDT setting
WDT setting was
was detected.
detected. (AL-Sta-
tus Code: 001F
hex)
An SM Event Mode
• An SM Event Mode that is not
that is not sup-
supported was set.
ported was set.
(AL-Status Code:
0028 hex)
An incorrect TxPDO
• An incorrect TxPDO was set,
was set. (AL-Status
e.g., the index, subindex, or
Code: 0024 hex)
size was outside of the allow-
able range.
An incorrect
• An incorrect RxPDO was set,
RxPDO was set.
e.g., the index, subindex, or
(AL-Status Code:
size was outside of the allow-
0025 hex)
able range.
An incorrect state
• An incorrect state transition
transition request
request was received.
was received.
(AL-Status Code:
0011 hex)
An unclear state
• An unclear state transition
transition request
request was received.
was received.
(AL-Status Code:
0012 hex)
When DC Mode
• When DC Mode was con-
was confirmed, the
firmed, the cycle time was set
cycle time was set
to a value that made operation
to a value that
impossible.
made operation
impossible.
(AL-Status Code:
0035 hex)
An error occurred in
• An NX Unit is not mounted
I/O data communi-
properly.
cations with the NX
• An NX Unit has failed.
Units.
Initializing an NX
• An error occurred in processing
Unit failed.
the EtherCAT Coupler Unit.
• An initialization error occurred
in an NX Unit.
• The Enabled Channel Settings
for all channels of the Analog
Input Unit are set to Disable.
The Enabled Channel Settings
for all channels of the Analog
Output Unit are set to Disable.
Process data com-
• The EtherCAT communications
munications were
cable is disconnected or bro-
stopped for more
ken.
than the specified
• There is an error in the host
period of time.
controller.
A synchronization
• The EtherCAT communications
interruption error
cable is disconnected or bro-
occurred.
ken.
• There is a synchronization set-
ting error in the EtherCAT Cou-
pler Unit.
• There is a hardware error in the
EtherCAT Coupler Unit.
Level
Maj
Prt
Min
Obs Info
NX-series EtherCAT Coupler Unit User's Manual (W519)
Reference
P. 13-29
P. 13-29
P. 13-30
P. 13-30
P. 13-31
P. 13-31
P. 13-32
P. 13-32
P. 13-33
P. 13-34
P. 13-34