Omron NX-ECC201 User Manual page 382

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

Appendices
Subin-
Index
dex
Object name
(hex)
(hex)
300A
---
Timestamp of Syn-
chronous IO Refresh
00
Number of entries
01
Timestamp of syn-
chronous input
02
Timestamp of syn-
chronous output
• This object gives the time stamps for when synchronous I/O refreshing was processed.
• Subindex 01 hex gives the time stamp for when the NX Unit performed synchronous inputs.
• Subindex 02 hex gives the time stamp for when the NX Unit performed synchronous outputs.
Subin-
Index
dex
Object name
(hex)
(hex)
3802
---
NX Unit Configura-
tion
00
Number of entries
01
NX Unit Configura-
tion set
04
NX Unit Serial Num-
ber Verification Set-
ting
• This object gives the management function of the configuration information for the EtherCAT Slave
Terminal.
• Subindex 01 hex tells whether the configuration information is set as confirmed or cancelled. The
configuration information consists of the Unit configuration information and I/O allocation information.
If the subindex is set to cancel, the Unit configuration information is created automatically. This
means the physical Unit configuration information is used, and no Unit configuration information is
registered separately.
0000 hex: Cancel configuration information
0001 hex: Confirm configuration information
• Subindex 04 hex gives the setting of the serial number check method for NX Units. If this subindex is
set to Setting = Actual device, the serial numbers of the NX Units are verified at these times: when
the power is turned ON and after the EtherCAT Coupler Unit is restarted. The serial numbers of the
NX Units saved in the Unit configuration information are compared with the actual device numbers of
the NX Units.
0000 hex: No check
0001 hex: Setting = Actual device
A - 42
Default
Data range
---
---
02 hex
02 hex
00000000000
000000000000
00000 hex
0000
to
FFFFFFFFFFF
FFFFFHex
00000000000
000000000000
00000 hex
0000
to
FFFFFFFFFFF
FFFFFHex
Default
Data range
---
---
04 hex
04 hex
0000 hex
0000
to
0001 hex
0000 hex
0000
to
0001 hex
Data
Unit
Size
attribute
---
---
---
---
---
1 byte
(U8)
ns
---
8 bytes
(U64)
ns
---
8 bytes
(U64)
Data
Unit
Size
Access
attribute
---
---
---
---
---
---
1 byte
RO
(U8)
---
R
2 bytes
RW
(U16)
---
R
2 bytes
RW
(U16)
NX-series EtherCAT Coupler Unit User's Manual (W519)
PDO
Com-
Access
map-
plete
ping
access
---
---
Not pos-
sible.
RO
Not
---
possi-
ble.
RO
Possi-
---
ble.
RO
Possi-
---
ble.
PDO
Com-
map-
plete
ping
access
---
Not pos-
sible.
Not
---
possi-
ble.
Not
---
possi-
ble.
Not
---
possi-
ble.