 Accessibility for Operation and Maintenance
• To ensure safe access for operation and maintenance, separate the EtherCAT Slave Terminal as
much as possible from high-voltage equipment and power machinery.
• If will be easy to operate the EtherCAT Slave Terminal if it is mounted at a height of 1.0 to 1.6 m
above the floor.
 Improving Noise Immunity
• Do not mount the EtherCAT Slave Terminal in a cabinet or control panel containing high-voltage
equipment.
• Install the EtherCAT Slave Terminal at least 200 mm away from power lines.
Power lines
200 mm
min.
EtherCAT Slave Terminal
• Ground the mounting plate between the EtherCAT Slave Terminal and the mounting surface.
 Installation Orientation
Refer to 6-1-3 Installation Orientation on page 6-8.
Installation Method in Control Panels
Mount the EtherCAT Slave Terminal on DIN Track if you install it in a cabinet or control panel.
Consider the width of wiring ducts, wiring, ventilation, and Unit replacement when determining the
space between EtherCAT Slave Terminals.
Additional Information
The EtherCAT Slave Terminal must be mounted on DIN Track.
It cannot be mounted with screws.
NX-series EtherCAT Coupler Unit User's Manual (W519)
200 mm min.
6 Installation