13 Troubleshooting
Event name
Unit Configuration Information Error
Meaning
An error occurred in the Unit configuration information in the EtherCAT Coupler Unit.
Source
EtherCAT Master Function Mod-
ule
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The power supply to the EtherCAT
Coupler Unit was turned OFF or
Sysmac Studio communications
were disconnected while down-
loading the Unit configuration
information.
Attached
None
information
Precautions/
None
Remarks
13 - 24
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Clear all of memory in the Ether-
CAT Coupler Unit, and then down-
load the Unit configuration
information again.
Event code
35000000 hex
EtherCAT Cou-
Detection
pler Unit
timing
Cycle power to
Log category
the EtherCAT
Coupler Unit or
restart the
Slave Terminal.
The Slave Terminal stops in Pre-Operational state.
I/O refreshing for the NX Units in the EtherCAT Slave
Terminal stops. Messages cannot be sent to the NX
Units in the EtherCAT Slave Terminal.
Name
---
Prevention
Do not turn OFF the power supply
to the EtherCAT Coupler Unit or
disconnect Sysmac Studio com-
munications while downloading
the Unit configuration information.
NX-series EtherCAT Coupler Unit User's Manual (W519)
When power is
turned ON to
the EtherCAT
Coupler Unit or
the Slave Ter-
minal is
restarted
System