6 Installation
Forced Ventilation by Fan at Top of Panel
Fan
Air filter
Forced Ventilation Method
Forced Air Circulation by Fan in Closed Panel
EtherCAT
Fan
Slave
Terminal
EtherCAT
Slave
Terminal
Forced Circulation Method
Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
Low Temperatures
The EtherCAT Slave Terminal may not start normally if the temperature is below 0°C when the power is
turned ON.
Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel.
Alternatively, leave the EtherCAT Slave Terminal power ON to keep the EtherCAT Slave Terminal
warm.
6 - 24
EtherCAT
Slave
Terminal
EtherCAT
Slave
Terminal
Air conditioner
Control panel
Room Cooling
NX-series EtherCAT Coupler Unit User's Manual (W519)