13 Troubleshooting
Event name
Memory Corruption Detected
Meaning
Memory corruption was detected.
Source
EtherCAT Master Function Mod-
ule
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
Memory corruption was detected.
Attached
None
information
Precautions/
None
Remarks
Event name
Unit Configuration Error, Too Many Units
Meaning
The number of connected NX Units exceeds the maximum value for the EtherCAT Coupler Unit.
Source
EtherCAT Master Function Mod-
ule
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
More than the maximum number
of NX Units is connected to the
EtherCAT Coupler Unit.
Attached
None
information
Precautions/
None
Remarks
13 - 22
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Cycle the power supply to the
EtherCAT Coupler Unit. If this
error occurs again even after you
cycle the power supply, replace
the EtherCAT Coupler Unit.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Reduce the number of NX Units
that are connected to the maxi-
mum number or fewer.
Event code
10430000 hex
EtherCAT Cou-
Detection
pler Unit
timing
Cycle the power
Log category
supply to the
EtherCAT Cou-
pler Unit.
I/O refreshing for the NX Units in the EtherCAT Slave
Terminal stops. Messages cannot be sent to the NX
Units in the EtherCAT Slave Terminal.
Name
---
Prevention
None
Event code
24A00000 hex
EtherCAT Cou-
Detection
pler Unit
timing
Cycle power to
Log category
the EtherCAT
Coupler Unit or
restart the
Slave Terminal.
The Slave Terminal stops in Pre-Operational state.
I/O refreshing for the NX Units in the EtherCAT Slave
Terminal stops. Messages cannot be sent to the NX
Units in the EtherCAT Slave Terminal.
Name
---
Prevention
Configure the EtherCAT Slave
Terminal within the maximum
number of NX Units.
NX-series EtherCAT Coupler Unit User's Manual (W519)
Continuously
System
When power is
turned ON to
the EtherCAT
Coupler Unit or
the Slave Ter-
minal is
restarted
System

Advertisement

Table of Contents
loading

Table of Contents