Omron NX-ECC201 User Manual page 379

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

Subin-
Index
dex
Object name
(hex)
(hex)
3005
---
NX Unit Message
Enabled Status
00
Number of entries
01
NX Unit Message
Enabled Status 15
02
NX Unit Message
Enabled Status 31
03
NX Unit Message
Enabled Status 63
04
NX Unit Message
Enabled Status 125
• This object tells whether message communications are enabled for the NX Units
• The number shown at the end of each object name for subindexes 01 to 04 hex gives the number of
NX Units for which the status is acquired. The data assignments are given in the following table. The
number in each cell is the NX Unit number of the corresponding NX Unit. NX Unit number 0 repre-
sents the EtherCAT Coupler Unit.
The applicable bit is 0 (FALSE) if message communications are disabled, or 1 (TRUE) if message
communications are enabled.
Message communications are disabled for NX Units that are set to Disable.
Word
offset
15
+0
15
+1
31
+2
47
+3
63
+4
79
+5
95
+6
111
+7
Refer to NX Unit Message Enabled Status under Details of I/O Data in the EtherCAT Coupler Unit on
page 9-16 for details on this status.
NX-series EtherCAT Coupler Unit User's Manual (W519)
Default
Data range
---
---
04 hex
04 hex
0000 hex
0000
to
FFFF hex
00000000
00000000
hex
to
FFFFFFFF hex
00000000000
000000000000
00000 hex
0000
to
FFFFFFFFFFF
FFFFF hex
00000000000
000000000000
00000000000
000000000000
0000000000
00000000
hex
to
3FFFFFFFFFF
FFFFFFFFFFF
FFFFFFFFFF
hex
14
13
12
11
10
14
13
12
11
10
30
29
28
27
26
46
45
44
43
42
62
61
60
59
58
78
77
76
75
74
94
93
92
91
90
110
109
108
107
106
125
124
123
122
Data
Unit
Size
attribute
---
---
---
---
---
1 byte
(U8)
---
---
ARRAY[0.
.1] OF
BYTE
---
---
ARRAY[0.
.3] OF
BYTE
---
---
ARRAY[0.
.7] OF
BYTE
---
---
ARRAY[0.
.15] OF
BYTE
Bit position
09
08
07
06
05
9
8
7
6
5
25
24
23
22
21
41
40
39
38
37
57
56
55
54
53
73
72
71
70
69
89
88
87
86
85
105
104
103
102
101
121
120
119
118
117
Appendices
PDO
Com-
Access
map-
plete
ping
access
---
---
Not pos-
sible.
RO
Not
---
possi-
ble.
RO
Possi-
---
ble.
RO
Possi-
---
ble.
RO
Possi-
---
ble.
RO
Possi-
---
ble.
04
03
02
01
00
4
3
2
1
0
20
19
18
17
16
36
35
34
33
32
52
51
50
49
48
68
67
66
65
64
84
83
82
81
80
100
99
98
97
96
116
115
114
113
112
A - 39
A

Advertisement

Table of Contents
loading