6 Installation
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Power supply
Power supply
Power supply
Parallel Wiring (Single Phase)
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the EtherCAT Slave Terminal is installed in a panel that includes
high-voltage devices. Whenever possible, wire and install them separately.
• Either install the EtherCAT Slave Terminal a minimum of 200 mm away from high-voltage lines or
power lines, or place the high-voltage lines or power lines in metal tubing and completely ground
the metal tubing to 100 Ω or less.
High-voltage power panel
Power lines
200 mm
EtherCAT
Slave
Terminal
Example: Separating EtherCAT Slave Terminal from Power Lines
 Other Precautions
Some models of Digital Input Units and Digital Output Units have polarity. Make sure that you wire
the polarity correctly.
6 - 30
NG
Conduits
Load
Incorrect
OK
Conduits
Load
Correct
Conduits
OK
Load
Correct
Power
lines
EtherCAT
Slave
200 mm
Terminal
Metal tubing
Ground to 100 Ω or less