Omron NX-ECC201 User Manual page 144

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

7 Wiring
Isolating the EtherCAT Slave Terminal from the Control Panel
If the ground wire for the EtherCAT Coupler Unit or an NX Unit with a ground terminal is shared with
power equipment, noise will adversely affect the Units.
You can use OMRON NX-AUX01 DIN Track Insulation Spacers with PFP-50N or PFP-100N DIN Tracks
to isolate an EtherCAT Slave Terminal from the control panel.
 Installing DIN Track Insulation Spacers and DIN Track
Secure the DIN Track Insulation Spacers to the control panel with screws, and then secure the DIN
Track to the DIN Track Insulation Spacers. The recommended tightening torque for M4 screws is 1.2
N·m.
DIN Track
Insulation Spacers
• DIN Track Insulation Spacers
NX-AUX01 (OMRON Corporation)
10
6
Precautions for Correct Use
If you use DIN Track Insulation Spacers to install an EtherCAT Slave Terminal, the height will be
increased by approximately 10 mm. Make sure that the EtherCAT Slave Terminal and connect-
ing cables do not come into contact with other devices.
7 - 12
DIN Track
Control panel
35
10
14.8
M4
Screws, M4×10
NX-series EtherCAT Coupler Unit User's Manual (W519)