Omron NX-ECC201 User Manual page 371

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

Subin-
Index
dex
Object name
(hex)
(hex)
1C12
---
Sync Manager 2
PDO Assignment
00
Number of assigned
RxPDOs
01 to
1st - 255th PDO
FF
Mapping object
index of assigned
PDO
*1. This is set to RO if the object does not have a receive PDO.
• This object gives the receive PDO that is used by Sync Manager 2.7There can be a maximum of 255
PDO mappings in the range of indexes from 1600 to 17F7 hex.
• The default value depends on the Unit configuration. The default value is 0000 hex for NX Units that
are not mounted.
Subin-
Index
dex
Object name
(hex)
(hex)
1C13
---
Sync Manager 3
PDO Assignment
00
Number of assigned
TxPDOs
01 to
1st - 255th PDO
FF
Mapping object
index of assigned
PDO
*1. This is set to RO if the object does not have a transmit PDO.
• This gives the transmit PDO that is used by the Sync Manager.
• There can be a maximum of 255 PDO mappings in the range of indexes from 1A00 to 1BF8 hex and
1BFF hex.
• The default value depends on the Unit configuration. The default values are 1BF8 and 1BFF hex for
NX Units that are not mounted.
NX-series EtherCAT Coupler Unit User's Manual (W519)
Default
Data range
---
---
00 hex
00 to FF hex
Depends on
0000 hex,
configuration.
1600 to 17F7
hex
Default
Data range
---
---
00 hex
00 to FF hex
Depends on
0000 hex,
configuration.
1A00 to 1BF8
hex,
1BFF hex
Data
Unit
Size
Access
attribute
---
---
---
---
---
B
1 byte
RW
(U8)
---
B
2 bytes
RW
(U16)
Data
Unit
Size
Access
attribute
---
---
---
---
---
B
1 byte
RW
(U8)
---
B
2 bytes
RW
(U16)
Appendices
PDO
Com-
map-
plete
ping
access
---
Possible.
Not
---
*1
possi-
ble.
Not
---
*1
possi-
ble.
PDO
Com-
map-
plete
ping
access
---
Possible.
Not
---
*1
possi-
ble.
Not
---
*1
possi-
ble.
A
A - 31