Omron NX-ECC201 User Manual page 339

Machine automation controller nx-series ethercat coupler unit
Table of Contents

Advertisement

Precautions for Correct Use
Checking the Serial Numbers of NX Units
If the Serial Number Check Method setting on the EtherCAT Coupler Unit is set to Setting =
Actual device, temporarily change this setting to None, and then replace the NX Unit. Get the
serial number of the new NX Unit, and then set the Serial Number Check Method setting on the
EtherCAT Coupler Unit to Setting = Actual device again.
If you replace the NX Unit with the Serial Number Check Method setting set to Setting = Actual
device, a Unit Configuration Verification Error will occur.
Refer to 9-2-3 Setting the Unit Configuration Information on page 9-8 for details on the Serial
Number Check Method setting for the EtherCAT Coupler Unit, and to 9-2-7 Sysmac Studio
Functions Used as Required on page 9-25 for details on getting the serial numbers of NX Units.
Additional Information
• Refer to the manual for the specific NX Unit for the procedures to mount and remove the NX
Unit.
• Refer to the NJ-series CPU Unit Built-in EtherCAT Port User's Manual (Cat. No. W505) for
the procedures to disconnect and connect the EtherCAT Coupler Unit from and to the Ether-
CAT network.
• Refer to NJ-series CPU Unit Software User's Manual (Cat. No. W501-E1-06 or later) for the
procedures for restoring and comparing data.
NX-series EtherCAT Coupler Unit User's Manual (W519)
14 Maintenance and Inspection
14
14 - 7

Advertisement