Event code
Event name
35000000 hex
Unit Configu-
ration Infor-
mation Error
35010000 hex
Unit Configu-
ration Verifi-
cation Error
35020000 hex
NX Unit
Minor Fault
35040000 hex
Mailbox Set-
ting Error
35050000 hex
RxPDO Set-
ting Error
35060000 hex
TxPDO Set-
ting Error
NX-series EtherCAT Coupler Unit User's Manual (W519)
Meaning
Assumed cause
An error occurred in
• The power supply to the Ether-
the Unit configura-
CAT Coupler Unit was turned
tion information in
OFF or Sysmac Studio commu-
the EtherCAT Cou-
nications were disconnected
pler Unit.
while downloading the Unit
configuration information.
There is an incon-
• An NX Unit that is registered in
the Unit configuration informa-
sistency between
tion is not connected.
the Unit configura-
tion information in
• A connected NX Unit does not
the EtherCAT Cou-
agree with the NX Unit that is
pler Unit and the
registered in the Unit configura-
Units that are actu-
tion information.
ally connected. Or,
• An NX Unit that is not regis-
the Unit configura-
tered in the Unit configuration
tion was changed
information is connected.
during operation
• A Unit that is disabled in the
while the Unit con-
Unit configuration information
figuration informa-
is mounted.
tion was not set in
• A Unit became disconnected
the EtherCAT Cou-
during operation while the Unit
pler Unit.
configuration information was
not set.
• A Unit was connected during
operation while the Unit config-
uration information was not set.
• The serial number of a Unit that
is registered in the Unit config-
uration information does not
agree with the serial number of
the Unit that is connected. (The
Serial Number Check Method
is set to Setting = Actual
device.)
• The version of a Unit that is
registered in the Unit configura-
tion information is newer than
the version of the Unit that is
connected.
• The power supply to an Addi-
tional NX Unit Power Supply
Unit is not turned ON.
A minor fault was
• A minor fault level error
detected in an NX
occurred in a Unit where an
Unit.
error was detected.
This event is recorded in the
event log in the Communica-
tions Coupler Unit.
An incorrect mail-
• An incorrect mailbox setting
box setting was
was detected for the Sync
detected for the
Manager.
Sync Manager.
(AL-Status Code:
0016 hex)
An error was
• An error was detected in the
detected in the
RxPDO settings.
RxPDO settings.
(AL-Status Code:
001D hex)
An error was
• An error was detected in the
detected in the
TxPDO settings.
TxPDO settings.
(AL-Status Code:
001E hex)
13 Troubleshooting
Level
Maj
Prt
Min
Obs
Info
P. 13-24
P. 13-25
P. 13-27
P. 13-27
P. 13-28
P. 13-28
Reference
13
13 - 15