Event name
NX Unit Minor Fault
Meaning
A minor fault was detected in an NX Unit.
Source
EtherCAT Master Function Mod-
ule
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
A minor fault level error occurred
in a Unit where an error was
detected.
This event is recorded in the event
log in the Communications Cou-
pler Unit.
Attached
None
information
Precautions/
None
Remarks
Event name
Mailbox Setting Error
Meaning
An incorrect mailbox setting was detected for the Sync Manager. (AL-Status Code: 0016 hex)
Source
EtherCAT Master Function Mod-
ule
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
An incorrect mailbox setting was
detected for the Sync Manager.
Attached
None
information
Precautions/
None
Remarks
NX-series EtherCAT Coupler Unit User's Manual (W519)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Check the cause of the minor fault
in the NX Unit.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Correct the mailbox setting and
then download the settings to the
EtherCAT master again.
13 Troubleshooting
Event code
35020000 hex
NX Unit
Detection
timing
Depends on the
Log category
error that
occurred.
Depends on the error that occurred.
Name
---
Prevention
---
Event code
35040000 hex
EtherCAT Cou-
Detection
pler Unit
timing
Reset the
Log category
EtherCAT mas-
ter parameters.
The Slave Terminal stops in Init state.
Name
---
Prevention
Set the communications for the
Slave Terminal that are set in the
EtherCAT master according to the
ESI.
Continuously
Depends on the
error that
occurred.
13
When moving
from Init state to
Pre-Operational
state.
System
13 - 27