Examples:
• For inverse output of "8: During baseblock", set 108.
• For inverse output of "4A: During KEB" set 14A.
n
H2-06: Watt Hour Output Unit Selection
When one of the multi-function terminals is set to output the number of watt hours (H2-01, H2-02, or H2-03 = 39), parameter
H2-06 determines the units for the output signal.
This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the frequency that
pulses are issued to keep track of the kWh for the drive.
No.
H2-06
Note:
1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.
Integral Power (every 100 ms)
(Multi-function Output)
u

H3: Multi-Function Analog Inputs

The drive is equipped with three multi-function analog input terminals: A1, A2, and A3.
Input Terminal Settings on page 118
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
H3-01
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and bias
settings will be read as 0%.
Setting 1: -10 to 10 Vdc
The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.
n
H3-02: Terminal A1 Function Selection
Selects the input signal level for analog input A1.
instructions on adjusting the signal level.
No.
H3-02
n
H3-03, H3-04: Terminal A1 Gain and Bias Settings
Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Parameter Name
Watt Hour Output Unit Selection
H2-06
(Pulse Output Unit)
H2-01 to 03
OFF
Figure 1.74 Watt Hour Output Example
for a listing of the functions that can be set to these terminals.
Name
Terminal A1 Signal Level Selection
Refer to Multi-Function Analog Input Terminal Settings on page 118
Name
Terminal A1 Function Selection
Setting Range
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
ON
OFF
0.2 s
Refer to Multi-Function Analog
Setting Range
0 to 1
Setting Range
1.7 H: Terminal Functions
Default
0
Default
0
Default
0
for
1
115