H3: Multi-Function Analog Inputs

No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal
(410)
Level Selection
H3-02
Terminal A1 Function
(434)
Selection
H3-03
Terminal A1 Gain
(411)
Setting
H3-04
Terminal A1 Bias
(412)
Setting
H3-09
Terminal A2 Signal
(417)
Level Selection
H3-10
Terminal A2 Function
(418)
Selection
H3-11
Terminal A2 Gain
(419)
Setting
H3-12
Terminal A2 Bias
(41A)
Setting
H3-13
Analog Input Filter Time
(41B)
Constant
H3-14
Analog Input Terminal
(41C)
Enable Selection
H3-16
Terminal A1 Offset
(2F0)
H3-17
Terminal A2 Offset
(2F1)
H3-oo
Function
Setting
0
Frequency bias
1
Frequency gain
Auxiliary frequency
reference 1
2
(used as a Multi-Step
Speed 2)
Auxiliary frequency
3
reference 2
(3rd step analog)
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
LCD Display
0: 0 to 10 V with zero limit
Term A1 Level
1: 0 to 10 V without zero limit
0: 0-10V,
2: 4-20 mA
(LowLim=0)
3: 0-20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A1.
Term A1 FuncSel
Sets the level of the input value selected in H3-02 when 10 V
is input at terminal A1.
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Terminal A1 Bias
0: 0 to 10 V with zero limit
Term A2 Level
1: 0 to 10 V without zero limit
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A2.
Term A2 FuncSel
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Terminal A2 Bias
Sets a primary delay filter time constant for terminals A1 and
A1/A2 Filter T
A2. Used for noise filtering.
Determines which analog input terminals will be enabled when
A1/A2 Sel
a digital input programmed for "Analog input enable"
1: A1 Available
(H1-oo = C) is activated.
2: A2 Available
1: Terminal A1 only
3: A1/A2 Available
2: Terminal A2 only
3: Terminals A1 and A2
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
Term A1 Offset
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
Term A2 Offset
H3 Multi-Function Analog Input Settings
LCD Display
Freq Ref Bias
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
Freq Ref Gain
of -100 to 0%.
10 V = E1-04 (maximum output frequency)
Aux Reference1
10 V = E1-04 (maximum output frequency)
Aux Reference2
B.7 H Parameters: Multi-Function Terminals
Description
Use jumper switch S1 to set input terminal A1
for current or voltage.
Use jumper switch S1 to set input terminal A2
for current or voltage input signal.
Description
Values
Page
Default: 0
170
Range: 0 to 3
Default: 0
170
Range: 0 to 26
Default: 100.0%
Min.: -999.9
130
Max.: 999.9
Default: 0.0%
Min.: -999.9
130
Max.: 999.9
Default: 2
170
Range: 0 to 3
Default: 0
171
Range: 0 to 26
Default: 100.0%
Min.: -999.9
131
Max.: 999.9
Default: 0.0%
Min.: -999.9
131
Max.: 999.9
Default: 0.03 s
Min.: 0.00
Max.: 2.00
Default: 2
Range: 1 to 3
Min.: -500
Max.: 500
Min.: -500
Max.: 500
Page
171
171
B
171
171
295