6. Direct encoder with position tracking for measuring gear:
p2506 * p0412
For a linear encoder, the following must be maintained:
- p0407 * p2503 / (2^p0419 * 10^7) <= 1.0
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07754
Drive: Incorrect shutoff valve configuration
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An incorrect shutoff valve configuration was detected.
Fault value (r0949, interpret decimal):
100:
Enable Safety Integrated (p9601/p9801), but p0218.0 = 0 (shutoff valve not available).
101:
The manipulated variable inhibit time is set less than the wait time to evaluate the feedback signal contacts when
switching on the shutoff valve (p0230 < p9625[0]/p9825[0]).
102:
The manipulated variable inhibit time is set less than the wait time to evaluate the feedback signal contacts when
switching off the shutoff valve (p0230 < p9625[1]/p9825[1]).
Remedy:
For fault value = 100:
Check the enable of Safety Integrated and the shutoff valve (p9601/p9801, p0218.0).
For fault value = 101:
Set the manipulated variable inhibit time higher than the wait time to evaluate the feedback signal contacts when
switching on the shutoff valve (p0230 > p9625[0]/p9825[0]).
For fault value = 102:
Set the manipulated variable inhibit time higher than the wait time to evaluate the feedback signal contacts when
switching off the shutoff valve (p0230 > p9625[1]/p9825[1]).
See also: p0230 (Drive filter type motor side)
F07800
Drive: No power unit present
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The power unit parameters cannot be read or no parameters are stored in the power unit.
It is possible that the DRIVE-CLiQ cable between the Control Unit and power unit is interrupted or defective.
Note:
This fault also occurs if an incorrect topology was selected in the commissioning software and this parameterization
is then downloaded to the Control Unit.
See also: r0200 (Power unit code number actual)
Remedy:
- carry out a POWER ON (power off/on) for all components.
- check the DRIVE-CLiQ cable between the Control Unit and power unit.
- Check the power unit and replace if necessary.
- check the Control Unit, and if required replace it.
- after correcting the topology, the parameters must be again downloaded using the commissioning software.