Siemens SINAMICS G150 Manual page 1750

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
- contact the Hotline.
- replace the TM54F.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
A35080 (F)
TM54F: Checksum error safety parameters
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The calculated checksum entered in r10004 over the safety-relevant parameters does not match the reference
checksum saved in p10005 at the last machine acceptance.
Fault value (r0949, interpret binary):
Bit 0 = 1: Checksum error for functional SI parameters.
Bit 1 = 1: Checksum error for SI parameters for component assignment.
Remedy:
- check the safety-relevant parameters and if required, correct.
- set the reference checksum to the actual checksum.
- acknowledge the hardware replacement.
- carry out a POWER ON (power off/on).
- carry out an acceptance test.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
A35081 (F)
TM54F: Static (steady state) 1 signal at the F-DI for safe acknowledgment
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
A logical 1 signal is present at the F-DI configured in p10006 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal
must be present. This avoids unintentional safety-relevant acknowledgement (or the "Internal Event Acknowledge"
signal) if a wire breaks or one of the two digital inputs bounces.
Remedy:
Set the fail-safe digital input (F-DI) to a logical 0 signal (p10006).
Note:
F-DI: Failsafe Digital Input
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
F35150
TM54F: Communication error
Message value:
%1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A communication error between the TM54F master and Control Unit or between the TM54F slave and the Motor
Module/Hydraulic Module was detected.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
When replacing a Motor Module/Hydraulic Module, carry out the following steps:
- start the copy function for the node identifier on the TM54F (p9700 = 1D hex).
- acknowledge the hardware CRC on the TM54F (p9701 = EC hex).
- save all parameters (p0977 = 1).
- carry out a POWER ON (power off/on) for all components.
1750
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents