4 Faults and alarms
4.2 List of faults and alarms
Example:
If the SI sampling cycle is 12 ms and the switching frequency is 110 ms (p10017 = 0), the maximum discrepancy time
which can be set is as follows:
p10002 <= 110/2 ms - 12 ms = 43 ms --> rounded-off, the following is obtained p10002 <= 36 ms
Since the discrepancy time can only be accepted as a whole SI sampling time, the value will need to be rounded up
or down to a whole SI sampling time value if it is not an exact integer multiple of an SI sampling time.
Basic secondary condition to set the discrepancy time:
The discrepancy time of the FDIs must always be set higher than the highest value p9780 (the drives that use safety
with TM54F).
F-DI: Failsafe Digital Input
F-DO: Failsafe Digital Output
F35152
TM54F: Internal software error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An internal software error has occurred in the Terminal Module 54F (TM54F).
The fail-safe digital inputs and digital outputs (F-DI, F-DO) on the TM54F have been set to the safe state.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Note:
F-DI: Failsafe Digital Input
F-DO: Failsafe Digital Output
Remedy:
Check that the firmware version of the TM54F matches the Control Unit's firmware version.
The automatic firmware update must be activated in the project.
Note:
This signal will also appear, for example, in conjunction with fault F35013. In this case you should check all the
parameters for the test stop on the TM54F (p10001, p10003, p10007, p10041, p10046, p10047). In this case, a
POWER ON is required after the parameters have been corrected.
A35200 (F, N)
TM: Calibration data
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, TM150, TM31, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected in the calibration data of the Terminal Module.
Alarm value (r2124, interpret decimal):
ddcbaa dec: dd = component number, c = AI/AO, b = fault type, aa = number
c = 0: analog input (AI, Analog Input)
c = 1: analog output (AO, Analog Output)
b = 0: No calibration data available.
b = 1: Offset too high (> 100 mV).
Remedy:
- carry out a POWER ON (power off/on) for all components.
- Replace the component if necessary.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
1752
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A