Remedy:
- check the monitoring time setting (p0255[0]).
- check the contactor wiring and activation.
- replace the contactor.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F30061 (A)
Bridging contactor monitoring
Message value:
Fault cause: %1 bin
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A feedback signal for the bypass contactor is interconnected and the monitoring activated.
After switching-in/switching-out the contactor, a correct feedback signal was not received within the monitoring time
set in p0255[1].
Fault value (r0949, interpret binary):
Bit 0: The time set in p0255[1] was exceeded when switching-in/switching-out the contactor.
Bit 1: The bypass contactor was opened in operation.
Bit 2: The bypass contactor was switched-in in the OFF state or during pre-charging.
Remedy:
- check the monitoring time setting (p0255[1]).
- check the contactor wiring and activation.
- replace the contactor.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A30065 (F, N)
Voltage measured values not plausible
Message value:
%1
Message class:
Power electronics faulted (5)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The voltage measurement supplies values that are not plausible
Bit01: Phase U.
Bit02: Phase V.
Bit03: Phase W.
Remedy:
- Deactivate voltage measurement (p247.0 = 0).
- Deactivate flying restart with voltage measurement (p247.5 = 0) and deactivate fast flying restart (p1780.11 = 0).
Reaction upon F:
NONE (OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F30070
Cycle requested by the power unit module not supported
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A cycle is requested that is not supported by the power unit.
Fault value (r0949, interpret hexadecimal):
0: The current control cycle is not supported.
1: The DRIVE-CLiQ cycle is not supported.
2: Internal timing problem (clearance between RX and TX instants too low).
3: Internal timing problem (TX instant too early).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1551