Remedy:
- Check the required interface configuration (p8940 and following), correct if necessary, and activate (p8945).
or
- Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8925 (PN interface configuration)
A08564
CBE20: Syntax error in configuration file
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A syntax error has been detected in the ASCII configuration file for the Communication Board Ethernet 20 (CBE20).
The saved configuration file has not been loaded.
Remedy:
- Check the CBE20 configuration (p8940 and following), correct if necessary, and activate (p8945 = 2).
Note:
The configuration is not applied until the next POWER ON!
- reconfigure the CBE20 (e.g. using the STARTER commissioning software)
See also: p8945 (CBE2x interface configuration)
A08565
PNCOMM BOARD : Consistency error affecting adjustable parameters
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8945) for the Communication Board Ethernet
20 (CBE20).
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
Note:
For all alarm values, the following applies: currently set configuration has not been activated.
DHCP: Dynamic Host Configuration Protocol
See also: p8940 (CBE2x Name of Station), p8941 (CBE2x IP Address of Station), p8942 (CBE2x Default Gateway of
Station), p8943 (CBE2x Subnet Mask of Station), p8944 (CBE2x DHCP Mode)
Remedy:
- Check the required interface configuration (p8940 and following), correct if necessary, and activate (p8945).
or
- Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8945 (CBE2x interface configuration)
F08700 (A)
CAN: Communications error
Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
Vector: OFF3 (NONE, OFF1, OFF2)
Infeed: NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A CAN communications error has occurred.
Fault value (r0949, interpret decimal):
1: The error counter for the send telegrams has exceeded the BUS OFF value 255. The bus disables the CAN
controller.
- bus cable short circuit.
- incorrect baud rate.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1523