A08758
CAN: Maximum number of valid PDO exceeded
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum number of valid PDO was exceeded.
Alarm value (r2124, interpret decimal):
1:
The total number of valid RPDO of all CANopen supported drive objects was exceeded.
As a result of the hardware, the limit is 25 valid RPDO.
2:
The total number of valid TPDO of all CANopen supported drive objects was exceeded.
The limit is defined by the following ratio:
CAN sampling time (p8848) / current controller sampling time (p0115[0])
Note:
RPDO: Receive Process Data Object
TPDO: Transmit Process Data Object
Remedy:
Comply with the limit for the maximum number of valid RPDO or TPDO.
Apply one of the following options to delete the alarm:
- POWER ON (off/on).
- carry out a warm restart (p0009 = 30, p0976 = 2).
- execute CANopen NMT command reset node.
- change CANopen NMT state.
- delete alarm buffer [0...7] (p2111 = 0).
Note:
The remaining available RPDO or TPDO are indicated in r8742.
See also: r8742 (CAN PDO available number)
A08759
CAN: PDO COB-ID already available
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An existing PDO COB-ID was allocated.
Remedy:
Select another PDO COB-ID.
A08760
CAN: maximum size of the IF PZD exceeded
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum size of the IF PZD was exceeded.
Alarm value (r2124, interpret decimal):
1: error for IF PZD receive.
2: error for IF PZD send.
Note:
IF: interface
Remedy:
Map fewer process data in PDO.
Apply one of the following options to delete the alarm:
- POWER ON (off/on).
- carry out a warm restart (p0009 = 30, p0976 = 2).
- execute CANopen NMT command reset node.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1527