4 Faults and alarms
4.2 List of faults and alarms
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35213 (F, N)
TM: Temperature alarm threshold channel 2 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[2]) has exceeded the
threshold value to initiate this alarm (p4102[4]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[2] = 1, 4), the following applies:
- if r4101[2] > 1650 ohms, the temperature r4105[2] = 250 °C
- if r4101[2] <= 1650 ohms, the temperature r4105[2] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[4] - hysteresis (5 K); for TM150, can be set using
p4118[2].
See also: p4102
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35214 (F, N)
TM: Temperature alarm threshold channel 3 exceeded
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
B_INF, TM150, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[3]) has exceeded the
threshold value to initiate this alarm (p4102[6]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[3] = 1, 4), the following applies:
- if r4101[3] > 1650 ohms, the temperature r4105[3] = 250 °C
- if r4101[3] <= 1650 ohms, the temperature r4105[3] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy:
- allow the temperature sensor to cool down to below p4102[6] - hysteresis (5 K); for TM150, can be set using
p4118[3].
See also: p4102
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35220 (N, A)
TM: Frequency limit reached for signal output
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
B_INF, TM31, VECTOR_G
Reaction:
Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The signals output from the Terminal Module 41 (TM41) for tracks A/B have reached the limit frequency. The output
signals are no longer in synchronism with the specified setpoint.