4 Faults and alarms
4.2 List of faults and alarms
Remedy:
For a fault value in the range from bit 0 ... 5:
- First check that all drives are entered in p10010,
extended safety functions or basic functions have been enabled via TM54F.
- Execute the copy function for TM54F(p9700 = 87).
- adapt the checksums for TM54F(p9701 = 172).
- copy RAM to ROM.
- carry out a POWER ON.
For a fault value in the range from bit 16 ... 21:
Increase the current controller sampling time of the corresponding drive, in order to avoid faults in operation.
- Execute the copy function for TM54F(p9700 = 87).
- adapt the checksums for TM54F(p9701 = 172).
- copy RAM to ROM.
- carry out a POWER ON.
F35005
TM54F:parallel connection not supported
Message value:
Fault cause: %1 bin
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The TM54F function with Basic Safety Functions is used. This function is not supported when power units are
connected in parallel.
All drives of the TM54F assume fail safe values, and are not enabled.
See also: p10010 (SI TM54F drive object assignment)
Remedy:
- deactivate parallel connection or TM54F with Basic Functions.
- copy RAM to ROM.
- carry out a POWER ON (power off/on).
F35006
TM54F: drive groups invalid
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The functionality of the basic functions via TM54F is used.
Drive groups have been incorrectly parameterized (incorrect parameter assignment).
Fault value (r0949, interpret binary):
The value specifies in which drive group Basic Safety drives are mixed with Extended Safety drives.
Bit 0 = 1 : drive group 1 error
Bit 1 = 1 : drive group 2 error
Bit 2 = 1 : drive group 3 error
Bit 3 = 1 : drive group 4 error
As long as this fault is present, fail safe values are activated in TM54F. All the drives are not enabled.
Note:
-this error is also signaled if a drive controlled with TM54F is parameterized so that the basic functions are controlled
via TM54F and simultaneously extended safety functions or ncSI have been parameterized.
Remedy:
Corresponding to the fault value, p10011 should be checked to ensure that no Basic Safety drives are mixed with
Extended Safety drives in a drive group.
1742
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A