Siemens SINAMICS G150 Manual page 1519

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

F08502 (A)
PN/COMM BOARD: Monitoring time sign-of-life expired
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
Vector: OFF1 (OFF2, OFF3)
Infeed: OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection to the COMM BOARD was interrupted.
Remedy:
- check communications link.
- check COMM BOARD.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A08504 (F)
PN/COMM BOARD: Internal cyclic data transfer error
Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic actual and/or setpoint values were not transferred within the specified times.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
Check the parameterizing telegram (Ti, To, Tdp, etc.).
Reaction upon F:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY
F08510 (A)
PN/COMM BOARD: Send configuration data invalid
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
Vector: OFF1 (OFF2, OFF3)
Infeed: OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
COMM BOARD did not accept the send-configuration data.
Fault value (r0949, interpret decimal):
Return value of the send-configuration data check.
Remedy:
Check the send configuration data.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A08511 (F)
PN/COMM BOARD: Receive configuration data invalid
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive unit did not accept the receive configuration data.
Alarm value (r2124, interpret decimal):
Return value of the receive configuration data check.
1: Connection established to more drive objects than configured in the device. The drive objects for process data
exchange and their sequence are defined in p0978.
2: Too many PZD data words for output or input to a drive object. The number of possible PZD items in a drive object
is determined by the number of indices in r2050/p2051 for PZD IF1, and in r8850/p8851 for PZD IF2.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1519

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents