4 Faults and alarms
4.2 List of faults and alarms
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A33463 (N)
Encoder 3: Analog sensor position value exceeds limit value
Message value:
%1
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The position value has exceeded the permissible range of -0.5 ... +0.5.
Alarm value (r2124, interpret decimal):
1: Position value from the LVDT sensor.
2: Position value from the encoder characteristic.
Remedy:
Re alarm value = 1:
- Check the LVDT ratio (p4678).
- check the reference signal connection at track B.
Re alarm value = 2:
- check the coefficients of the characteristic (p4663 ... p4666).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A33470 (F, N)
Encoder 3: Soiling detected
Message value:
-
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the case of the alternative encoder system interface on the Sensor Module Cabinet 30 (SMC30), encoder soiling is
signaled via a 0 signal at terminal X521.7.
Remedy:
- check the plug connections.
- replace the encoder or encoder cable.
Reaction upon F:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F33500 (N, A)
Encoder 3: Position tracking traversing range exceeded
Message value:
-
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
VECTOR_G
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
For a configured linear axis without modulo correction, the drive/encoder has exceeded the maximum possible
traversing range. The value should be read in p0412 and interpreted as the number of motor revolutions.
For p0411.0 = 1, the maximum traversing range for the configured linear axis is defined to be 64x (+/- 32x) of p0421.
For p0411.3 = 1, the maximum traversing range for the configured linear axis is pre-set (default value) to the highest
possible value and is +/-p0412/2 (rounded off to complete revolutions). The highest possible value depends on the
pulse number (p0408) and the fine resolution (p0419).
Remedy:
The fault should be resolved as follows:
- select encoder commissioning (p0010 = 4).
- reset the position tracking as follows (p0411.2 = 1).
- de-select encoder commissioning (p0010 = 0).
The fault should then be acknowledged and the absolute encoder adjusted.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
1708
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A