Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (power off/on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F30835
Power unit DRIVE-CLiQ: Cyclic data transfer error
Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the power unit concerned. The nodes do
not send and receive in synchronism.
Fault cause:
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON.
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F30836
Power unit DRIVE-CLiQ: Send error for DRIVE-CLiQ data
Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the power unit concerned. Data were not
able to be sent.
Fault cause:
65 (= 41 hex):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Carry out a POWER ON.
F30837
Power unit DRIVE-CLiQ: Component fault
Message value:
Component number: %1, fault cause: %2
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component concerned. Faulty hardware cannot be excluded.
Fault cause:
32 (= 20 hex):
Error in the telegram header.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1585