A07805 (N)
Infeed: Power unit overload I2t
Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
B_INF
Reaction:
NONE
Acknowledge:
NONE
Cause:
Alarm threshold for I2t overload (p0294) of the power unit exceeded.
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F07807
Drive: Short-circuit/ground fault detected
Message value:
%1
Message class:
Ground fault / inter-phase short-circuit detected (7)
Drive object:
VECTOR_G
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
A phase-phase short-circuit or ground fault was detected at the motor-side output terminals of the converter.
Fault value (r0949, interpret decimal):
1: Short-circuit, phases U-V
2: Short-circuit, phases U-W
3: Short-circuit, phases V-W
4: Ground fault with overcurrent
1xxxx: Ground fault with current in phase U detected (xxxx = component of the current in phase V in per mille)
2xxxx: Ground fault with current in phase V detected (xxxx = component of the current in phase U in per mille)
Note:
Also when interchanging the line and motor cables is identified as a motor-side short circuit.
Connecting to a motor that is either not de-energized or partially de-energized is possibly detected as ground fault.
Remedy:
- check the motor-side converter connection for a phase-phase short-circuit.
- rule-out interchanged line and motor cables.
- check for a ground fault.
For a ground fault:
- do not enable the pulses when connecting to a rotating motor without the "Flying restart" function activated (p1200).
- increase the de-energization time (p0347).
- If required, deactivate the monitoring (p1901).
F07808 (A)
HF damping module: damping not ready
Message value:
New message: %1
Message class:
Power electronics faulted (5)
Drive object:
VECTOR_G
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When switching on or in the switched-on state, the HF damping module does not return a ready signal.
Remedy:
- Check the DRIVE-CLiQ wiring to the HF damping module.
- check the 24 V supply voltage.
- if required, replace the HF damping module.
Note:
HF Damping Module
Reaction upon A:
NONE
Acknowl. upon A:
NONE
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1485