Siemens SINAMICS G150 Manual page 1697

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

F33151 (N, A)
Encoder 3: Encoder speed for initialization AB too high
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowledge:
PULSE INHIBIT
Cause:
The encoder speed is too high while initializing the Sensor Module.
Remedy:
Reduce the speed of the encoder accordingly during initialization.
If necessary, de-activate monitoring (p0437.29).
See also: p0437 (Sensor Module configuration extended)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F33152 (N, A)
Encoder 3: Maximum input frequency exceeded
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowledge:
PULSE INHIBIT
Cause:
The maximum input frequency of the encoder evaluation has been exceeded.
Fault value (r0949, interpret decimal):
Actual input frequency in Hz.
See also: p0408 (Rotary encoder pulse number)
Remedy:
- Reduce the speed.
- Use an encoder with a lower pulse number (p0408).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F33153 (N, A)
Encoder 3: Identification error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred when identifying the encoder (waiting) p0400=10100.
The connected encoder was not able to be identified.
Fault value (r0949, interpret hexadecimal):
Bit 0: Data length incorrect
See also: p0400 (Encoder type selection)
Remedy:
Manually configure the encoder according to the data sheet.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1697

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents