Siemens SINAMICS G150 Manual page 1545

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Remedy:
Replace the capacitor fan in the power unit.
F30040
Power unit: Undervolt 24 V
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for CU310-2, CUA31 and CUA32 the undervoltage threshold is 16 V.
- for all other power units, the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- Check the power supply of the power unit.
- carry out a POWER ON (power off/on) for the component.
F30040
Power unit: Undervolt 24 V
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
B_INF
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The undervoltage threshold of the 24 V power supply for the power unit was fallen below for longer than 3 ms.
Note:
- for booksize power units, the undervoltage threshold is 15 V.
- for all other power units, the undervoltage threshold depends on the power unit, and is not displayed.
Fault value (r0949, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- Check the power supply of the power unit.
- carry out a POWER ON (power off/on) for the component.
A30041 (F)
Power unit: Undervoltage 24 V alarm
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret decimal):
24 V voltage [0.1 V].
Remedy:
- Check the power supply of the power unit.
- carry out a POWER ON (power off/on) for the component.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
A30041 (F)
Power unit: Undervoltage 24 V alarm
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
B_INF
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1545