Omron CPM1 - PROGRAMING MANUAL 02-2001 Programming Manual page 93

Hide thumbs Also See for CPM1 - PROGRAMING MANUAL 02-2001:
Table of Contents

Advertisement

CPM2A/CPM2C High-speed Counters
PC Setup
72
Note The following examples are for Fujitsu-compatible connectors. Input bit ad-
dresses and connector pin numbers depend on the models. Refer to the CPM2C
Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for de-
tails.
Input terminals
Input connector
(See above note.)
The following table shows the settings in the PC Setup area related to interrupt
input usage.
Word
Bits
DM 6628
00 to 03
04 to 07
08 to 11
12 to 15
Note *Input number 00005 and 00006 cannot be used in CPM2C CPU Units with 10
I/O points and in CPM2C-S CPU Units.
The setting will go into effect when the mode is changed (from PROGRAM to
MONITOR/RUN) or when the power supply is turned ON to the CPM2A/
CPM2C.
00004: Input interrupt (counter mode) 1
00003: Input interrupt (counter mode) 0
00006: Input interrupt (counter mode) 3
00005: Input interrupt (counter mode) 2
00004: Input interrupt (counter mode) 1
00003: Input interrupt (counter mode) 0
Note Inputs 00006 and 00005 cannot
be used with CPU Units that
have only 10 I/O points.
Function
0: Normal input
Interrupt setting for
input 00003
1: Interrupt input
1: Interrupt input
Interrupt setting for
(interrupt input mode or
input 00004
counter mode)
counter mode)
Interrupt setting for
2: Quick-response input
input 00005*
Interrupt setting for
input 00006*
Section
2-2
Setting
1

Hide quick links:

Advertisement

Table of Contents
loading