Omron CPM1 - PROGRAMING MANUAL 02-2001 Programming Manual page 232

Hide thumbs Also See for CPM1 - PROGRAMING MANUAL 02-2001:
Table of Contents

Advertisement

Temperature Sensor Units
25315
(First Scan Flag)
25313
(Always ON Flag)
02000
02001
(continued next page.)
212
25506(=)
00213 (open-circuit detected)
00215 (leftmost digits)
00215 (leftmost digits)
00215 (rightmost digits)
(1)
MOV (21)
Sets DM 0103 and DM 0102 to
#0000
#0100 and #0000, respectively.
DM0102
MOV (21)
#0100
DM0103
CMP (20)
Detects completion of input 0 initialization.
002
#7FFE
ON when input 0 has been initialized.
02000
Open-circuit alarm output
01000
SET 02001
Ready for data conversion.
(2)
MOV (21)
Leftmost digits moved to IR 200
002
200
(3)
MOVD (83)
Leftmost and rightmost digits
002
rearranged and moved to
#0020
IR 202 and IR 201.
201
(4)
MOVD (83)
200
#0300
201
(5)
MOVD (83)
200
#0011
202
RSET 02001
RSET 02002
Data rearrangement completed.