Pulse Output Instructions
Operation in Continuous
Mode
Flags
7-27-3 ACCELERATION CONTROL – ACC(––)
ACC(––)
P
M
C
Limitations
Description
In continuous mode, pulses will be output indefinitely until stopped by executing
INI(61) with C=003, executing SPED(64) again with F=0000, or switching the
PC to PROGRAM mode.
Pulse frequency
ER:
A data area boundary is exceeded.
Indirectly addressed DM word is non-existent. (Content of *DM word is
not BCD, or the DM area boundary has been exceeded.)
P is not 000 or 010, M is not 000 or 001, or F is not 0000 to 1000.
SPED(64) is executed in an interrupt subroutine while a pulse I/O or
high-speed
SPED(64), PULS(65), ACC(––), PWM(––), or SYNC(––)) is being
executed in the main program.
Ladder Symbols
@ACC(––)
P
M
C
This instruction is available in the CPM2A/CPM2C only.
P must be 001 or 002 and M must be 000 to 003.
C to C+3 must be in the same data area.
ACC(––) is used to specify the acceleration/deceleration rate and start the pulse
output for a pulse output with trapezoidal acceleration and deceleration.
In general, ACC(––) should be executed just once each time that the accelera-
tion/deceleration rate needs to be set; use the differentiated variation
(@ACC(––)) or an input condition that is ON for just one cycle.
Note Refer to 2-5 Pulse Output Functions for more details.
Port Specifier (P)
Always set the port specifier to 000. The 000 setting specifies single-phase
pulse output 0 with trapezoidal acceleration and deceleration.
counter
instruction
(INI(61),
Operand Data Areas
000, 002, or 010 to 013
C: First control word
IR, SR, AR, DM, HR, LR
Section
Time
PRV(62),
CTBL(63),
P: Port specifier
000
M: Mode specifier
7-27
491