Temperature Sensor Units
25313
(Always ON Flag)
25313
(Always ON Flag)
02000
Execution condition
02001
Execution condition
CMP (20)
25506(=)
CMP (20)
25506
CMP (20)
25506(=)
CMP (20)
25505(>)
25507(<)
BCD (24)
CMP (20)
25506(=)
CMP (20)
25505(>)
25507(<)
BCD (24)
Detects completion of input 0 initialization.
001
#7FFE
ON when input 0 has been initialized
02000
Detects completion of input 1 initialization.
002
#7FFE
02001
ON when input 1 has been initialized
Detects an open-circuit alarm or Unit error by check-
ing converted temperature data for the error code
001
7FFF.
#7FFF
ON when an open-circuit alarm or Unit error has been
01000
detected for input 0.
Checks to see if the temperature data in IR 001 has
exceeded 500.0 C (1388 Hex without decimal point).
001
#1388
01001
ON for an input 0 temperature error
Converts the contents of IR 001 (temperature data
for input 0) to BCD and stores the result in
001
DM 0000.
DM0000
Detects an open-circuit alarm or Unit error by check-
ing converted temperature data for the error code
002
7FFF.
#7FFF
ON when an open-circuit alarm or Unit error has been
01002
detected for input 1.
Checks to see if the temperature data in IR 002 has
exceeded 500.0 C (1388 Hex without decimal point).
002
#1388
ON for an input 1 temperature error
01003
Converts the contents of IR 002 (temperature data
for input 1) to BCD and stores the result in
002
DM 0001.
DM0001