I/O Allocation for CPM1/CPM1A/CPM2A PCs
Example: Configuration Including Analog I/O Unit, Temperature Sensor Unit, and Expansion I/O Unit
CPU Unit
(60 I/O points)
36 inputs
IR 00000 to IR 00011
IR 00100 to IR 00111
IR 00200 to IR 00211
24 outputs
IR 01000 to IR 01007
IR 01100 to IR 01107
IR 01200 to IR 01207
Bits
15
14
IR 000
Do not use
IR 001
Do not use
IR 002
Do not use
Inputs
IR 003
IR 004
IR 005
IR 006
IR 007
Do not use
IR 010
IR 011
IR 012
Outputs
IR 013
IR 014
322
Analog I/O Unit
CPM1A-MAD01/11
2 analog inputs
Input 0: IR 003
Input 1: IR 004
1 analog output
Output 1: IR 013
13
12
11
10
09
Used for input 0 of the Analog I/O Unit
Used for input 1 of the Analog I/O Unit
Used for input 0 of the Temperature Sensor Unit
Used for input 1 of the Temperature Sensor Unit
Used for the output of the Analog I/O Unit
With the exception of CPM1A-TS002/102 Temperature Sensor Units, up to 3
Expansion Units (Analog I/O Units, Temperature Sensor Units, or CompoBus/S
Units) can be connected to a CPM1A or CPM2A PC. Only one
CPM1A-TS002/102 Temperature Sensor Unit can be connected. (See page
323 for an example of CPM1A-TS002/102 allocations.)
Temperature Sensor Unit
CPM1A-TS001/101
2 temperature inputs
Input 0: IR 005
Input 1: IR 006
No outputs
08
07
06
05
Section
Expansion I/O Unit
(20 I/O points)
16 inputs
IR 00700 to IR 00711
8 outputs
IR 01400 to IR 01407
04
03
02
01
00