CompoBus/S I/O Master Functions (SRM1(-V2) and CPM2C-S Only)
Status Flags
Uppermost bits: Slave Communications Error Flags
Word
15
14
13
AR04
OUT
OUT
OUT
7
6
5
AR05
IN7
IN6
IN5
AR06
OUT
OUT
OUT
15
14
13
AR07
IN15
IN14
IN13
SRM1 (-V2)
or CPM2C-S
CompoBus/S
communications path
3. CompoBus/S Terminals with 16 points can be set for only even number ad-
dresses.
4. Analog Terminals can be set for only even number addresses.
The communications status between CompoBus/S terminals is output through
AR04 to AR07 Slave Add Flags and Slave Communications Error Flags.
12
11
10
9
OUT
OUT
OUT
OUT
4
3
2
1
IN4
IN3
IN2
IN1
OUT
OUT
OUT
OUT
12
11
10
9
IN12
IN11
IN10
IN9
Note
1. IN0 to IN15 are the input terminals and OUT0 to OUT15 are the output termi-
nals.
2. When the maximum number of CompoBus/S units is set to 16, IN8 to IN15
and OUT8 to OUT15 cannot be used.
3. The Slave Add Flag turns ON when a slave joins the communications. When
the power to the CPU Unit is turned OFF and ON again all bits will turn OFF.
4. The Slave Communications Error Flag turns ON when a slave participating
in the network is separated from the network. The bit will turn OFF when the
slave re-enters the network.
5. For the SRM1, an error will not occur even if the same node address is allo-
cated to more than one slave. Errors will also not occur when communica-
tions go down or communications errors, such as broken lines, occur. Set all
node addresses very carefully and confirm slave operation by including a
section of ladder program using the Status Flags. An example is shown be-
low.
Example
Disconnection (2)
IR 000
Bits 00 to 07
Slave 1
Node 0 (IN0)
Lower Bits: Slave Add Flags
8
7
6
5
OUT
OUT
OUT
OUT
0
7
6
5
IN0
IN7
IN6
IN5
OUT
OUT
OUT
OUT
8
15
14
13
IN8
IN15
IN14
IN13
IR 001
Bits 00 to 07
Slave 2
Node 2 (IN2)
Section
4
3
2
1
OUT
OUT
OUT
OUT
4
3
2
1
IN4
IN3
IN2
IN1
OUT
OUT
OUT
OUT
12
11
10
9
IN12
IN11
IN10
IN9
IR 000
Bits 00 to 07
Node address
duplication (1)
Slave 3
Node 0 (IN0)
2-12
0
OUT
0
IN0
OUT
8
IN8
149