Orientalmotor AZX Series Operating Manual page 223

Hide thumbs Also See for AZX Series:
Table of Contents

Advertisement

Information bit
Information item
output signal
Tripmeter
INFO-TRIP
Odometer
INFO-ODO
Torque
INFO-TRQ
Settling time
INFO-STLTIME
Start operation
INFO-DSLMTD
restricted mode
I/O test mode
INFO-IOTEST
Configuration
INFO-CFG
request
Reboot request
INFO-RBT
If the "Preset request" information was generated for 100 ms or more in a state where the Information
auto clear (41BFh) was set to disable, the preset may have been failed. There are the following two
possible reasons the preset was failed.
- The ABZO sensor is not connected to the driver.
- Preset was executed in a state where the position deviation between the command position and
the actual position was 1.8 degrees or more.
Cause
The travel distance of the motor exceeded
the value set in the Tripmeter information
(41AFh).
The cumulative travel distance of the
motor exceeded the value set in the
Odometer information (41B0h).
The detection torque of the motor
exceeded the value set in the Torque
information (41A7h).
The settling time exceeded the value set in
the Settling time information (41B5h).
• Configuration was executed.
• "Remote operation" was executed with
the MEXE02 software.
• Data was written from the MEXE02
software to the driver.
• "Restore to factory settings" was executed
with the MEXE02 software.
• Configuration was executed.
• "I/O test" was executed with the MEXE02
software.
Configuration was requested to execute.
Reboot was requested.
Information
Clear condition
After one of the following operations
was performed, the travel distance
(Tripmeter) of the motor fell below the
value set in the Tripmeter information
(41AFh).
• The Tripmeter information (41AFh)
was set again.
• The Clear tripmeter (40CFh) of the
maintenance command was
executed.
After the following operation was
performed, the cumulative travel
distance (Odometer) of the motor fell
below the value set in the Odometer
information (41B0h).
• The Odometer information (41B0h)
was set again.
The detection torque of the motor fell
below the value set in the Torque
information (41A7h).
• Operation was started.
• The settling time fell below the value
set in the Settling time information
(41B5h).
• Configuration was completed.
• Remote operation was canceled.
• Writing data was completed.
• Data was restored to the factory
setting.
• Configuration was completed.
• The I/O test mode was canceled.
Configuration was executed.
Reboot was executed.
223