Mains
Short circuit current rating
Line fusing
As baseline there is no integrated fuse or circuit breaker. The option 3008-3 Mains
connector/Fuse includes integrated circuit breaker.
Robot
IRB 460
IRB 660
IRB 2600
IRB 4600
IRB 5710
IRB 5720
IRB 6650S
IRB 6660
IRB 6700
IRB 6710
IRB 6720
IRB 6730
IRB 6740
Residual current
An external earth fault protection (residual current device, RCD) is required. For
detailed information on how to select an external earth fault protection, see
Connecting incoming mains and protective earth to the controller on page
Product manual - OmniCore V250XT Type B
3HAC087112-001 Revision: A
2.2 Technical data for OmniCore V250XT Type B controller
Note
If the controller is to be installed where the specified voltage (see table above)
is not available, the customer is required to provide an external transformer.
Voltage (V)
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
380 VAC-480 VAC, 3-phase
Note
For details about installations according to UL requirements, see
incoming mains and protective earth to the controller on page
Note
The integrator is responsible to address local electrical requirements.
© Copyright 2023-2023 ABB. All rights reserved.
2 Controller description
Value
According to rating label.
Note
For installations according to UL require-
ments, short circuit current rating is 5 kA.
Current (A)
3x32 A
3x32 A
3x16 A
3x32 A
3x32 A
3x32 A
3x32 A
3x32 A
3x32 A
3x32 A
3x32 A
3x32 A
3x32 A
84.
Continues on next page
Continued
Connecting
84.
41