7 Troubleshooting
7.2.1 No LEDs are lit on the controller
Continued
Detailed working procedure
1
2
3
4
5
6
7
8
350
Action
Make sure that the mains switch (Q0) has been
switched on.
Make sure that the system is supplied with power.
•
Measure incoming mains voltage and make
sure the voltage is within the normal range.
Check that the mains connection (X0) is properly
connected.
Tip
For more details, see Circuit diagram - OmniCore
V250XT, rev 04 or later.
Check that the AC input cable is properly connec-
ted.
Check the output voltage of (Q0).
•
Make sure that (Q0) is closed.
Check the fuse (F1).
Check connector A1.X1.
Check the LED status.
© Copyright 2023-2023 ABB. All rights reserved.
Note
Use a multimeter and insulating
gloves.
If incoming mains is not ok, the
problem is not in the robot control-
ler. Troubleshoot incoming mains.
Use a multimeter and insulating
gloves.
Replace if damaged.
•
If abnormal, troubleshoot
the power unit. See
Troubleshooting the power
unit on page
•
If abnormal, troubleshoot
the LEDs. See
Troubleshooting LEDs in the
controller on page
Product manual - OmniCore V250XT Type B
3HAC087112-001 Revision: A
383.
368.