Write Window Interface - Mitsubishi Electric M80V Series Manual

Hide thumbs Also See for M80V Series:
Table of Contents

Advertisement

M800V/M80V Series PLC Interface Manual
5 Appx.1: PLC window
5.2 PLC Window Interface

5.2.3 Write Window Interface

 Writing control window
(Area where both PLC and NC set data)
R register
Writing control
window
RB
RB+1
RB+2
RB+3
RB+4
RB+5
RB+6
RB+7
(*1) These items are set by PLC.
(*2) This item is set by NC.
(*3) Turn ON the control signal after setting Section No., Section sub-ID No., Sub-section No., Data No., Writing method,
Number to be written, and write data 1 to 4 in the write data window.
 Write data window (Area where PLC sets data)
R register
RB+8 to 9
Write data window
RB+10 to 11
RB+12 to 13
RB+14 to 15
Item
Control signal(*1)(*3)
Data will be written by turning bit0 ON. NC and PLC write asynchronously.
When the writing is finished, the bit0 under "Status" of the writing result turns
ON.
When the bit0 under "Status" turns ON, turn OFF the bit0 of the control sig-
nal.
Section No.(*1)
Designate data type
Section sub-ID No.(*1) Designate part system No. (1 to maximum number of part system for each
model)
Sub-section No.(*1)
Designate data
Data No.(*1)
Designate axis No. used in the part system and variable No., etc.
(The axis No. is 1 to maximum number of axes for each model)
Writing method(*1)
0: Write up to 4 consecutive data from the designated data No.
1: Write up to 4 consecutive data from the designated sub-section No.
2: Write up to 4 consecutive data from the designated section sub-ID No.
Number to be writ-
Designate number of data to be written.
ten(*1)
Maximum number of data to be written is 4. If 5 or more is designated, the
number of data is regarded as 4.
Writing results(*2)
<Status> (bit0 to bit7)
bit0: Write finished (It turns ON when the writing is finished regardless of
writing successfulness)
bit1: Blank
bit2 to 7: Write error
The value and its meaning when the control signal is ON are as below:
0x01: Normally finished
0x41: Address illegal
0x45: Section No. illegal
0x49: Sub-section No. illegal
0x59: Not fit in the buffer
0x5D: Data type illegal
0x6D: Written in read-only data
0x79: Unable to write data
0x81: Axis designation illegal
0x85: Data No. illegal
<Results> (bit8 to bitF)
Number of data written
Item
Write data 1
Write data 2
Write data 3
Write data 4
Details
Details
Store the write data.
705
IB-1501616-D