M800V/M80V Series PLC Interface Manual
4 Explanation of Interface Signals
4.4 PLC Output Signals (Data Type: R***)
Cont.
Signal name
A
Chopping override
[Function]
This signal is used to designate the override value for the operation between the upper dead center and the bottom dead
center of the chopping axis.
[Operation]
Set the override value (0% to 100%) for the operation between the upper dead center and the bottom dead center with
a numerical value.
If a value outside the range is set, the override value is 100%.
Select the setting unit 1% or 0.01% with the control data "the setting unit of the chopping override".
(Example) When the setting unit is 1% and R2503 is set to "100" (0x0064), the override value is 100%.
When the setting unit is 0.01% and R2503 is set to "10000" (0x2710), the override value is 100%.
When the override value is set to "0", the operation error (M01 0150) occurs.
As for the override value for the operation between the basic position and the upper dead center, select valid or invalid
with the control data "rapid traverse override valid/invalid". When it is valid, rapid traverse override (code method or
value-setting method) is performed.
[Related signals]
(1) Chopping (YC30: CHPS)
(2) Chopping parameter valid (YC34)
(3) Chopping control data address (R2587)
(4) Rapid traverse override method selection (YC6F: ROVS, R2502)
(5) Rapid traverse override code 1,2 (YC68: ROV1, YC69: ROV2)
Abbrev.
$1
$2
CHPOV
R2503
R2703
R2903
559
$3
$4
$5
$6
R3103
R3303
R3503
$7
$8
R3703
R3903
IB-1501616-D