M800V/M80V Series PLC Interface Manual
4 Explanation of Interface Signals
4.1 PLC Input Signals (Bit Type: X***)
Cont.
Signal name
A
Hob axis delay excess
[Function]
This signal informs that after the spindle rotation speed synchronization is completed in the tool spindle synchronization II
(Hobbing), the hob axis tracking delay between the actual position and the commanded position has exceeded the
allowable delay angle.
Note
(1) This signal uses the 1st spindle signal regardless of the hob spindle's number.
[Operation]
This signal turns ON when:
 The spindle rotation speed synchronization has been completed and the maximum delay angle of the hob axis (spindle)
exceeded the delay allowable angle set in the parameter "#3133 spherr".
This signal turns OFF when:
 The tool spindle synchronization II is canceled.
Note
(1) Refer to the signal of the 1st spindle when the parameter "#1440 multi_sp_syn" (Multiple spindle synchronization
valid) is set to "0".
(2) Refer to the signal of the hob axis when the parameter "#1440 multi_sp_syn" (Multiple spindle synchronization valid)
is set to "1".
[Timing chart]
In tool spindle synchronization II
NC→PLC SPSYN3
Spindle rotation speed
synchronization completion
NC→PLC FSPRV
Hob axis delay excess
NC→PLC PHOVR
Maximum hob axis delay angle
NC→PLC
[Related signals]
(1) In tool spindle synchronization II (SPSYN3: X18AE)
(2) Spindle rotation speed synchronization completion (FSPRV: X18A9)
(3) Spindle synchronization Maximum phase error/Maximum hob axis delay angle (R6517)
Cont.
Signal name
A
Holding power of spindle increased
[Function]
The increase holding power of spindle (disturbance observer) state is output to this signal.
[Operation]
This signal turns ON when the "Increase holding power of spindle" signal (EXOBS) turns ON and the spindle drive unit
enables the disturbance observer.
Turning OFF the "Increase holding power of spindle" signal (EXOBS) turns this signal OFF.
[Related signals]
(1) Increase holding power of spindle (EXOBS: Y1893)
IB-1501616-D
Abbrev.
1stSP
PHOVR
X18B3
ON(G114.3)
+spherr
-spherr
Abbrev.
1stSP
EXOFN
X18B5
2ndSP
3rdSP
4thSP
X1913
X1973
X19D3
Monitoring area
2ndSP
3rdSP
4thSP
X1915
X1975
X19D5
268
5thSP
6thSP
7thSP
8thSP
X1A33
X1A93
X1AF3
X1B53
OFF(G113)
Delay allowable angle
#3133 spherr
5thSP
6thSP
7thSP
8thSP
X1A35
X1A95
X1AF5
X1B55